Monthly Hot & Cold Temperature Monitoring

CWH, HPOU hot water heaters >15 litres
Flush nearest outlet for 1 minute and record temperature. Record maximum temperature if hot water is flushed away within 1 minute.
​
Hot water system
Test sentinel outlets and ensure the hot water is ≥50°C (≥55°C in healthcare) after one minute of flushing. Check hot water return temperature on principal loops and flow temperature of subordinate loops.
​
Tanked and mains cold water systems
Test temperature of sentinel points and on long runs of pipe work to ensure water is <20°C after 2 minutes of flushing
Calorifier + PHE
Test temperature of flow and return. Flow temperature should be ≥60°C; return ≥50°C (55°C in healthcare)