Monthly Hot & Cold Temperature Monitoring

pme1013LegionellaF_Figure2_slide_edited.

CWH, HPOU hot water heaters >15 litres

Flush nearest outlet for 1 minute and record temperature. Record maximum temperature if hot water is flushed away within 1 minute.

​

Hot water system

Test sentinel outlets and ensure the hot water is ≥50°C (≥55°C in healthcare) after one minute of flushing. Check hot water return temperature on principal loops and flow temperature of subordinate loops.

​

Tanked and mains cold water systems

Test temperature of sentinel points and on long runs of pipe work to ensure water is <20°C after 2 minutes of flushing

 

Calorifier + PHE

Test temperature of flow and return. Flow temperature should be ≥60°C; return ≥50°C (55°C in healthcare)

 